General Certification CE, FCC class A Connectors 1 x Plug-in screw terminal (# 14 ~ 22 AWG) Enclosure ABS+PC Power Consumption 0.63 W (max.) Thermocouple Input Accuracy Voltage mode: ±0.1% or better Current mode: ±0.2% or better Bandwidth 13.1 Hz @ 50 Hz 15.72 Hz @ 60 Hz Channels 7 (differential, each channel can be configured with different range) CMR @ 50/60 Hz 92 dB min Input Impedance 20 MΩ. (Build-in 120 Ω Register for Current Input) lnput Range and Types Thermocouple J 0 ~ 760°C K 0 ~ 1,370°C T -100 ~ 400°C E 0 ~ 1,000°C R 500 ~ 1,750°C S 500 ~ 1,750°C B 500 ~ 1,800°C Current ±20 mA, 4 ~ 20 mA Voltage ±15 mV (0.2%), ±50 mV, ±100 mV, ±500 mV ±1 V, ±2.5 V Resolution 16-bit Sampling Rate 10 samples/sec. (total) Span Drift ±25 PPM/°C Zero Drift ±6 μV/°C High Common Mode 200 VDC Protection Fault and Withstands overvoltage up Overvoltage to ±35 V Protection Isolation Voltage 3,000 VDC Filter function Yes Built-in TVS/ESD Protection Note: Not support ADAM-5510KW series
订货信息:ADAM-5018P 7-ch Thermo. Input Module
w/ Ind. Input Range